Commissioning
12.9 Identification and maintenance data
Automation system
286 System Manual, 01/2023, A5E03461182-AK
H
Provides information about parameter
changes on the module
IM_PROFILE_SPECIFIC_TYPE read (2 bytes)
H
H
Provides information on the ID data ver-
sion
(0101
H = Version 1.1)
• IM_Version_Major
• IM_Version_Minor
IM_SUPPORTED read (2 bytes) 000EH provides information about the available
identification and maintenance data
Maintenance data 1: (Record index AFF1H)
Enter an identifier for the module here,
that is unique plant-wide.
Enter the installation location of the
module here.
Maintenance data 2: (Record index AFF2H)
IM_DATE read/write (16
YYYY-MM-DD HH:MM Enter the installation date of the module
Maintenance data 3: (Record index AFF3H)
Enter a comment about the module here.
Reading I&M records with record 255 (distributed configuration via PROFIBUS)
Use Read data record ("RDREC" instruction) to access specific identification data.
The modules support standardized access to identification data using DR 255 (index 65000 to
65003). For more information on the DR 255 data structure, refer to the specifications of the
Profile Guidelines Part 1: Identification & Maintenance Functions - Order no.: 3.502,
Version 1.2, October 2009.
The specifications are available, for example, on the PROFIBUS & PROFINET International (PI)
website on the Internet (https://www.profibus.com/).