Installation
6.7 Installing the interface module
Automation system
System Manual, 01/2023, A5E03461182-AK
145
Installing the interface module
Watch video sequence (https://support.industry.siemens.com/cs/ww/en/view/67462859)
To install an interface module, proceed as follows:
1. Mount the U-connector on the back right-hand side of the interface module.
2. Hook the interface module on the rail.
3. Pivot the interface module towards the back.
4. Tighten the interface module (tightening torque 1.5 Nm).
Figure 6-12 Installing the interface module
Uninstalling the interface module
The interface module is wired and is followed by additional modules.
To uninstall the interface module, follow these steps:
1. Switch off the supply voltage for the interface module.
2. Open the front cover.
3. Loosen the bus connector and the connector for the supply voltage with the screwdriver.
4. Remove the plug from the interface module.
5. Loosen the fixing screw of the interface module.
6. Pivot the interface module out of the mounting rail.