Flexible automation concepts
11.2 Configuration control (option handling)
Automation system
System Manual, 01/2023, A5E03461182-AK
251
Error messages
In case of error, the WRREC instruction returns the following error messages via the STATUS
block parameter:
Table 11- 9 Error messages
Error code
Meaning
80B1H
Invalid length; the length information in data record 196 is not correct.
80B5H
Configuration control parameters not assigned.
80E2
H
Data record was transferred in the wrong OB context. The data record must be
transferred in the startup program.
80B8
H
Parameter error
Reasons for a parameter error are:
Incorrect block ID in the header (not equal to 196)
Invalid version identifier in the header
A reserved bit was set
A station master slot was assigned an invalid slot in the station option
Multiple slots in the station master are assigned to the same slot in the station
option
For shared device on submodule level: violation of defined restrictions