Commissioning
12.7 Backing up and restoring the CPU configuration
Automation system
System Manual, 01/2023, A5E03461182-AK
275
Overview of backup types
The table below shows the backup of CPU data depending on the selected type of backup and
its specific characteristics:
Table 12- 5 Types of backup
Backup from
online device
Upload from de-
vice (software)
Upload device as
new station
Snapshot of the
monitor values
Current values of all DBs
(global and instance data blocks)
1
Blocks of the type OB, FC, FB and
DB
--
PLC tags
(tag names and constant names)
--
Technology objects
--
Hardware configuration
--
--
Actual values (bit memories, timers
and counters)
1
--
--
--
Content of the SIMATIC memory
card
--
2
--
Archives, recipes
--
--
--
Entries in the diagnostics buffer
--
--
--
--
Current time
--
--
--
--
Properties of the type of backup
Backup possible for fail-safe CPUs
Backup can be edited
--
Backup possible in operating mode
STOP
RUN, STOP
RUN, STOP
RUN, STOP
1
Only the values of the tags that are set as retentive are saved.
2
Contents of the DataLogs, Recipes and UserFiles folders
Example: Backup from online device
The following example shows how to carry out a complete backup of the current device state
of the CPU in STEP 7. The S7-1500 automation system is in RUN mode. Before the backup, the
CPU goes into STOP mode.
To start the backup, proceed as follows:
1. Right-click to select the CPU in the project tree.
2. Select the "Backup from online device" command from the shortcut menu.
The "Upload preview" dialog window sets out the key information on the backup process to
be run. For a backup you have to switch the CPU to the STOP mode.
3. In the "Action" column, select the "Stop module" command from the drop-down menu.
4. Click "Upload from device". The CPU changes to STOP mode. The backup of the CPU data
starts. The backup is saved in the project tree in the folder of the CPU under "Online
backups".