System overview
4.2 Configuration
Automation system
System Manual, 01/2023, A5E03461182-AK
47
Configuration example of the ET 200MP with fail-safe I/O modules
Interface module
I/O modules
Power supply (optional)
Fail-safe I/O modules
Mounting rail with integrated top-hat rail
Figure 4-13 Configuration example of the ET 200MP with fail-safe I/O modules
Hardware and software requirements
You use the S7-1500/ET 200MP fail-safe I/O modules:
In S7-1500 with S7-1500 F-CPUs as of firmware version V1.7
Distributed in ET 200MP with S7-1500 F-CPUs as of firmware version V1.5 and all F-CPUs
that can be selected in the hardware catalog of the TIA Portal
Fail-safe I/O modules in ET 200MP require the following interface modules:
IM 155-5 PN BA, as of firmware version V4.3
IM 155-5 PN ST, as of firmware version V3.0.0
IM 155-5 PN HF, as of firmware version V3.0.0
IM 155-5 DP ST, as of firmware version V3.0.0
To configure and program fail-safe I/O modules S7-1500/ET 200MP , you need:
STEP 7, V13 SP1 or higher
The option package STEP 7 Safety Advanced as of V13 SP1 + HSP0086