Fail-Safe signal module (SM) I/O configuration
5.2 Configuring common F-parameters
S7-1200 Functional Safety Manual
106 Manual, 02/2015, A5E03470344-AA
5.2
Configuring common F-parameters
Table 5- 1 Common F-parameters
F-parameters
Description
Default
Options
Manual assignment of
F-monitoring time
You must select the check box to change
F-monitoring time from the central value propa-
gated by the fail-safe CPU.
Check box
deselected
Check box:
Selected
Deselected
F-monitoring time
1
Watchdog timer monitoring safety-related
communication between the fail-safe CPU and
fail-safe SM (PROFIsafe monitoring time)
150 ms 1 to 65535 ms
F-source address Unique network-wide address for the fail-safe
CPU
1 You can configure the
F-source address
using the fail-safe
CPU parameter "Basis
for PROFIsafe ad-
dresses".
F-destination address CPU-wide unique address (usually in descend-
ing order, starting with 65534).
- 1 to 65534
Behavior after channel
fault
Response by the fail-safe SM to channel faults
such as a short-circuit, overload, or discrepancy
error.
Passivate channel Not configurable in the
fail-safe SM
Reintegration after
channel fault
(not available for the SM
1226 F-DQ 2 x Relay)
You have two methods, manual and automatic,
to reintegrate your fail-safe SM channels after a
channel fault. You can choose to reintegrate in
one of three ways:
All channels automatically (no acknowl-
edgement necessary for reintegration)
All channels manually (acknowledgement
necessary for reintegration)
Adjustable (channel-by-channel; some
channels automatically reintegrated and
some channels manually reintegrated)
Adjustable
Adjustable
All channels
automatically
All channels
manually
1
You set the "Default F-monitoring time for central F-IO" in the F-parameters of the fail-safe CPU. STEP 7 uses this
number to set the F-monitoring time in each fail-safe SM unless you select the check box for "Manual Assignment of F-
monitoring time" in that module configuration and assign a different time.
Refer to the SIMATIC, Industrial Software, SIMATIC Safety - Configuring and Programming,
Programming and Operating Manual
(http://support.automation.siemens.com/WW/view/en/54110126/0/en)
for further F-parameter
information
.

Table of Contents

Other manuals for Siemens SIMATIC S7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7 and is the answer not in the manual?

Siemens SIMATIC S7 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC S7
CategoryController
LanguageEnglish

Related product manuals