Technical specifications
A.1 General technical specifications
S7-1200 Functional Safety Manual
Manual, 02/2015, A5E03470344-AA
137
A.1.8
Environmental conditions
Table A- 5 Transport and storage
Environmental conditions - Transport and storage
EN 60068-2-2, Test Bb, Dry heat and
EN 60068-2-1, Test Ab, Cold
-40 °C to +70 °C
EN 60068-2-30, Test Db, Damp heat 25 °C to 55 °C, 95% humidity
EN 60068-2-14, Test Na, temperature shock
-40 °C to +70 °C, dwell time 3 hours, 5 cycles
EN 60068-2-32, Free fall 0.3 m, 5 times, product packaging
Atmospheric pressure
1080 to 660h Pa (corresponding to an altitude of -1000 to 3500m)
Table A- 6 Operating conditions
Environmental conditions - Operating
Ambient temperature range
(Inlet Air 25 mm below unit)
0 °C to 55 °C horizontal mounting
0 °C to 45 °C vertical mounting
95% non-condensing humidity
Atmospheric pressure
1080 to 795 hPa (corresponding to an altitude of -1000 to 2000m)
Concentration of contaminants
S0
2
: < 0.5 ppm; H
2
S: < 0.1 ppm; RH < 60% non-condensing
EN 60068-2-14, Test Nb, temperature change
5 °C to 55 °C, 3 °C/minute
EN 60068-2-27 Mechanical shock
15 G, 11 ms pulse, 6 shocks in each of 3 axis
EN 60068-2-6 Sinusoidal vibration DIN rail mount: 3.5 mm from 5-9 Hz, 1G from 9 - 150 Hz
Panel Mount: 7.0 mm from 5-9 Hz, 2G from 9 to 150 Hz
10 sweeps each axis, 1 octave per minute
Table A- 7 High potential isolation test
High potential isolation test
2
24 V/5 V nominal circuits
520 VDC (type test of optical isolation boundaries)
115/230 V circuits to ground
1500 VAC
115/230 V circuits to 115/230 V circuits
1500 VAC
115 V/230V circuits to 24 V/5 V circuits
1500 VAC (3000 VAC / 4242 VDC type test)
Ethernet port to 24 V/5 V circuits and ground
1
1500 VAC (type test only)
1
Ethernet port isolation is designed to limit hazard during short term network faults to hazardous voltages. It does not
conform to safety requirements for routine AC line voltage isolation.
2
SM 1226 F-DQ 2 x Relay has higher test voltages. See data sheet for that product.