Fail-Safe signal module (SM) applications
3.1 Digital input applications
S7-1200 Functional Safety Manual
72 Manual, 02/2015, A5E03470344-AA
3.1.5
Applications 7 and 8: 1oo2 evaluation of 3-wire, non-equivalent sensor circuit
In non-equivalent mode, short-circuit testing can be enabled on a 3-wire circuit. The module
expects that the logic "0" circuit will not change with the sensor dark test.
Figure 3-7 F-DI Application mode 7: Internal sensor supply
Figure 3-8 F-DI Application mode 8: External sensor supply