EasyManuals Logo

Siemens SIMATIC S7 Functional Safety Manual

Siemens SIMATIC S7
212 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #107 background imageLoading...
Page #107 background image
Fail-Safe signal module (SM) I/O configuration
5.3 Configuring SM 1226 F-DI 16 x 24 VDC DI and channel parameters
S7-1200 Functional Safety Manual
Manual, 02/2015, A5E03470344-AA
107
5.3
Configuring SM 1226 F-DI 16 x 24 VDC DI and channel parameters
Table 5- 2 SM 1226 F-DI 16 x 24 VDC DI parameters
DI parameters
Description
Default
Options
Short-circuit test This test creates short duration OFF pulses on
the sensor power supplies. Input circuits pow-
ered by Vs1 and Vs2 are expected to be OFF
during the sensor OFF time. Failure to detect
OFF when a sensor supply is OFF indicates a
short-circuit to a power source or another fault
that prevents the input from properly detecting
a "0". Input channels which fail this test are
passivated.
During the test, the reported process value will
not change, so the configured "Duration of
short-circuit test" increases the response time.
An actual process "0" occuring near the begin-
ning of a test will not be reported to the user
program until after the "Duration of short-circuit
test" time has elapsed.
The check box must be selected to activate the
short-circuit test.
Check box dese-
lected
Check box:
Selected
Deselected
Interval for short-circuit
test (see T_int in figure
below)
This value is the time between the OFF pulses
of the sensor supply.
Refer to the figure below for further information.
Note: The interval must be a minimum of eight
times the duration.
25.6 ms
12.8 ms
25.6 ms
51.2 ms
102.4 ms
204.8 ms
409.6 ms
819.2 ms
Duration of short-circuit
test (see T_dur in figure
below)
This value is the time that the power supply
remains off during the test. The short-circuit
test OFF pulse must be long enough for the
external sensors and wiring to respond and
present a "0" to the inputs.
Refer to the figure below for further information.
Note: The interval must be a minimum of eight
times the duration.
1.6 ms
1.6 ms
3.2 ms
6.4 ms
12.8 ms
Vsx
Vs1 or Vs2 sensor supplies (VDC)
T_int
Short-circuit test interval (time period) between the OFF pulses of the sensor supply
T_dur
Short-circuit test OFF pulse time duration (msec)

Table of Contents

Other manuals for Siemens SIMATIC S7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7 and is the answer not in the manual?

Siemens SIMATIC S7 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC S7
CategoryController
LanguageEnglish

Related product manuals