Fail-Safe signal module (SM) I/O configuration
5.4 Configuring SM 1226 F-DQ 4 x 24 VDC DQ and channel parameters
S7-1200 Functional Safety Manual
Manual, 02/2015, A5E03470344-AA
113
WARNING
In the presence of a single fault, the bit pattern tests can apply energy to the load for a
duration up to the configured "Maximum readback time switch on test".
If the load can respond dangerously within the configured readback time, it can respond to
bit pattern tests in the presence of a single fault, resulting in death or serious injury to
personnel and/or property damage.
Always choose a maximum readback configuration time that is guaranteed not to activate
the load.