Fail-Safe signal module (SM) diagnostics
6.2 Fault diagnostics
S7-1200 Functional Safety Manual
Manual, 02/2015, A5E03470344-AA
127
Event ID
Diagnostic mes-
sage
Fail-safe signal
module
Description
Possible causes
Corrective measures
1
0x0302 Discrepancy fail-
ure,
channel state 1/0
SM 1226 F-DI
16 x 24 VDC
External discrepancy
failure: Channel state
1/0 with 1oo2 equiva-
lent configuration
Short-circuit
Sensor mechan-
ical activation or
alignment out of
tolerance
sors are mounted and
aligned to be activated
together.
0x0303 Discrepancy fail-
ure,
channel state 1/1
SM 1226 F-DI
16 x 24 VDC
External discrepancy
failure: Channel state
1/1 with 1oo2 non-
equivalent configura-
tion
0x0306 Internal sensor
supply
short-circuit
to P
SM 1226 F-DI
16 x 24 VDC
SM provided sensor
supply voltage short-
ed to P
Sensor supply
shorted to P
Eliminate the short-
circuit.
Once the fault is
eliminated, the power
must
be switched off and on.
Short-circuit test
duration configured
too short
Increase short-circuit test
duration.
Failed sensor supply
Replace the fail-safe SM.
0x0307 Overload or inter-
nal sensor supply
shorted to ground
SM 1226 F-DI
16 x 24 VDC
Internal sensor sup-
ply
voltage shorted to M,
ground, or excessive
load on sensor sup-
ply
Short-circuit
Eliminate the short-
circuit.
Once the fault has been
eliminated, the power
must
be switched off and on.
Excessive load on
sensor supply
Reduce load on sensor
supply.
Failed sensor supply
Replace the fail-safe SM.
0x030B Channel failure
acknowledgement
All Channel configured
for manual acknowl-
edgement is ready to
reintegrate
Manual acknowl-
edgement required
Manually acknowledge
correction of channel fault
so that reintegration can
occur.
0x0311 Frequency too
high
SM 1226 F-DQ
4 x 24 VDC
SM 1226 F-DQ
2 x Relay
Switching frequency
exceeded; readback
not in time
Process value from
safety program
changing too rapidly
for SM to follow
Change Safety program
logic to guarantee more
time between output
changes.
0x0312 Undertemperature All
Under-
temperature at
microcomputers
Under-
temperature at
I/O
Shutdown due to
violation of low
temperature limit
value in the SM
case
Check the ambient
temperature.
Once the fault
has been eliminated,
the
power must be
switched off
and on.