Technical specifications
A.2 Fail-Safe CPU technical specifications
S7-1200 Functional Safety Manual
154 Manual, 02/2015, A5E03470344-AA
Isolation (group-to-group) 1500 VAC
1
--
Inductive clamp voltage -- L+ minus 48 VDC,
Switching delay (Qa.0 to Qa.3) 10 ms max. 1.0 μs max., off to on
Switching delay (Qa.4 to Qb.1) 10 ms max. 50 μs max., off to on
Maximum relay switching frequency
Pulse Train Output rate
Not recommended
2
100 kHz (Qa.0 to Qa.3)
3
, 2 Hz min.
3
Lifetime mechanical (no load)
10,000,000 open/close cycles
Lifetime contacts at rated load
100,000 open/close cycles
Last value or substitute value (default value 0)
Number of outputs on simultaneously
10 outputs at 55 °C horizontal or 45 °C vertical
500 m shielded, 150 m unshielded
Relay group-to-group isolation separates line voltage from SELV/PELV and separates different phases up to 250 VAC
line to ground.
For CPU models with relay outputs, you must install a digital signal board (SB) to use the pulse outputs.
Depending on your pulse receiver and cable, an additional load resistor (at least 10% of rated current) may improve
pulse signal quality and noise immunity.
4