Data Exchange with the Central Controller
IP244
C79000–B8576–C860–02
4–42
Byte 21 Main control byte 6
Number of standard
controllers
One Two Three Four Five Six Seven
Hot channel zones
0 to 5 0 to 5 0 to 5 0 to 5 0 to 5 0 to 5 0 to 5
Standard controller zones
6 6 and 7 6 to 8 6 to 9 6 to 10 6 to 11 6 to 12
Minimum possible sampling
times for hot channel
controller for ADC
conversion time 50 ms
400 ms 400 ms 400 ms 400 ms 400 ms 400 ms 400 ms
Minimum possible sampling
times for standard controller
for ADC conversion time 50
ms
480 ms 800 ms 1200 ms 1600 ms 2000 ms 2400 ms 2800 ms
Minimum possible sampling
times for hot channel
controller for ADC
conversion time 60 ms
480 ms 480 ms 480 ms 480 ms 480 ms 480 ms 480 ms
Minimum possible sampling
times for standard controller
for ADC conversion time 60
ms
480 ms 960 ms 1440 ms 1920 ms 2400 ms 2880 ms 3360 ms
Maximum value of
temperature increase
(C/min) permitted during
selfĆtuning of the standard
controllers at an ADC
conversion time of 50 ms
273 136 91 68 54 45 39
Maximum value of
temperature increase
(C/min) permitted during
selfĆtuning of the standard
controllers at an ADC
conversion time of 60 ms
227 113 75 56 45 37 32
If mixed operation has been selected, the IP cannot execute the following functions simultaneously:
– special function
– heating current monitoring
– Pt 100 operation
– processing of channels 13 and 14
– comparator
– pure hot channel control and
– cascaded control.