EasyManua.ls Logo

Siemens SIMATIC S7 - Messages 0 to 12 (Controller Parameters)

Siemens SIMATIC S7
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Data Exchange with the Central Controller
4–25
IP244
C79000–B8576–C860–02
2.1 Messages 0 to 12 (Controller Parameters)
Each message contains the setpoints and the parameters for the individual controller. (The second
parameters sets are stored in messages 30 to 42.)
HeatingĆcooling parameters
Control byte 2
Manual manipulated variable
Limit value (C)
SelfĆtuning parameters
0 to 50 %, 1 unit = 1 %
0 to 255 %, 1 unit = 1 % only if main control byte 1,
bit 2=0, otherwise free
Temperature setpoint
1st positive tolerance
1st negative tolerance
Lower setpoint
2nd positive tolerance
2nd negative tolerance
Control byte 1
Gain K
R
(ST)
0 to 1600 °C in 1°CĆsteps
1 to 255 °Cin1°CĆsteps
0 to 1599 °C in 1°CĆsteps
1 to 255 °Cin1°CĆsteps
1 to 255 °Cin1°CĆsteps
0 to 100 % or 128 to 228 % for negative numbers, 1 unit = 1 %
1 to 25599,1unit = KR = 0.01
1 to 255 °Cin1°CĆsteps
Evaluation factor (C)
Free
Sampling time T
A
(ST)
0 to 255 ğ,
1 unit =1ğ
0 to 255 %, 1 unit = 1 %
350 to 65535 ms, 1 unit = 1ms
if main control byte 1, Bit 2=0 /or for cooling only
350 to 392700 ms, 1 unit = 10 ms
if main control byte 1, Bit 2=1 and no cooling controller is
selected
only for cascaded
control
Integral action time T
N
(ST)
Upper limit of control zone (ST)
or setpoint ramping
Lower limit of control zone (ST)
HeatingĆcooling ratio (ST)
Message number
0 or (T
A
T
N
512 T
A
), 1 unit = 4 s
0 or (T
A
T
D
512 T
A
), 1 unit = 1 s
2
0 to 12
Parameters marked with (ST) need not be specified for
controllers with selfĆtuning
Response value
1 unit = 10 ° C Checkback signal for selfĆtuning function
If temperature values
are specified in °F:
T [° F]=T [° C]·1.8+32
Parameters marked with (C) are only valid for
cascaded control
0
1
2
3
0 to 1600 °C/h, 0 to 3000 °C/h or 0 to 2047 °F/h
(= 1137 °C/h) (ramp slope)
With 3Ćstep controllers and main control byte 1,
bit 2 = 1 the upper limit of the control zone is relative
to 200° C (see pages 34 and 35)
0 to 1600° C
Minimum jump for 3Ćstep controllers
Checkback signal for selfĆtuning function
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
Derivative action time T
D
(ST)
Fig. 2.1/1 Structure of messages 0 to 12

Table of Contents

Other manuals for Siemens SIMATIC S7

Related product manuals