Appendix
A Notes on Operating the IP 244 with the
Self-Tuning Function with FB 162 for
64 Messages
A.1 Requirements
A.1.1 Controlled System
The controlled system must permit a physical setpoint jump of 37 _C for 2-step
controllers or up to 110 _C for 3-step controllers.
The controlled system must demonstrate low pass characteristics.
The rate of rise of the actual value must not exceed maximum 60 _C/min at full
heating power or when simultaneously heating and cooling or the actual value may
not fall more than 60 _C/min.
The maximum rise of the actual value must be 0.05 _C/min with full heating
power.
The heating procedure must not take longer than 12 hours.
With pure Pt 100 operation only 11.6 h is permitted.
    
 
S and ADC conversion time = 50 ms, only 7.2 h permitted
S and ADC conversion time = 60 ms, only 8.7 h permitted
If only the cooling is active, you must guarantee that the actual value falls.
Suitable for systems in which no very large step-like disturbances (in the
automation control sense) occur.
A.1.2 Parameter Assignment
Main control byte 1, bit 2 = 1
DL n + 11, bit 1 = 1
Controller has heating output
No hot channel controller
No master controller with cascaded control
A.2 Recommended Procedure for Single Self-Tuning Function
A.2.1 All the parameters not marked with ”ST” in messages 0 to 12 and 30 to 42 must have
values assigned and the controller must be disabled using setpoint 0 or by setting the
heating switch to ”Off”. This prevents an unnecessary heating up before the
self-tuning function is started.
A.2.2 Generate an upward edge in bit 7 in the data byte n + 11 by means of the commands
”ST”, ”CR” or ”PA”. (The user must make sure to allocate the data byte DLn + 11
correctly.)

Table of Contents

Other manuals for Siemens SIMATIC S7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7 and is the answer not in the manual?

Siemens SIMATIC S7 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC S7
CategoryController
LanguageEnglish

Related product manuals