EasyManua.ls Logo

Siemens SIMATIC S7 - Assigning Parameters for the Self-Tuning Function; Which Controlled Systems Can the Self-Tuning Function be Used with

Siemens SIMATIC S7
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description of the Firmware
4–21
IP244
C79000–B8576–C860–02
1.2.4 Which Controlled Systems Can the Self-Tuning Function
be Used With?
The self-tuning function can be used with systems which meet the following conditions:
The system must display a low pass response. This condition is generally met by
temperature processes.
The control system must allow for the following temperature jump:
at least 37 °C with 2Ćstep controllers,
at least 37 °C up to 110 °C with 2Ćstep controllers.
The maximum rate of rise of the actual value must not exceed 60 °C/min with full heating
power or with simultaneous full heating and cooling power.
The maximum rise of the actual value must be  0.05 °C/min with full heating power.
The heating procedure must not require more than 12 hours.
With pure Pt 100 operation only 11.6 h is permitted.
With mixed operation and one
standard controller
and ADC conversion time = 50 ms, only 7.2 h permitted
and ADC conversion time = 60 ms, only 8.7 h permitted.
If only the cooling is active, you must guarantee that the actual value falls.
A further condition for calculating the cooling parameters is that the actual value must not
fall faster than 60 °C/min while the selfĆtuning function is heating and cooling
simultaneously.
Suitable for systems in which no large stepĆlike disturbances (in the automation control sense)
occur.
To convert to degrees Fahrenheit T [ F] = (T C] x1.8 + 32).
1.2.5 Assigning Parameters for the Self-Tuning Function
Each of the 13 temperature controllers can be assigned parameters to operate as a standard or
self-tuning temperature controller. This allows mixed controlled systems, some meeting the
required conditions and some not meeting the required conditions, to be operated with one
temperature controller module.
The self-tuning function is specified in messages 0 to 12 in the ”self-tuning” byte (byte 22).
The self-tuning function and the end of the self-tuning phase are indicated in a separate bit for
heating and cooling.
If only heating parameters and no cooling parameters have been calculated for a 3-step controller,
this is also indicated and a value for the required temperature jump is calculated and indicated to
the user.
While a controller is running with selfĆtuning function and determines parameters, it can
only be accessed by reading (if you try to assign parameters to the controller, the message
"parameter error" is output at the FB 162).

Table of Contents

Other manuals for Siemens SIMATIC S7

Related product manuals