EasyManua.ls Logo

Siemens SIMATIC S7 - Determining the System Parameters for 2;3-Step Controllers (When Main Control Byte 1, Bit 2 = 0)

Siemens SIMATIC S7
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Notes on Controller Settings
4–137
IP244
C79000–B8576–C860–02
4.6 Determining the System Parameters for 2/3-Step
Controllers (when Main Control Byte 1, Bit 2 = 0)
The heating and cooling curves of temperature-controlled systems are plotted with a recorder (see
Fig. 4.6/1).
The procedure is as follows:
main control byte 1, bit 2 = 0
entry of non-critical control parameters
T
A
= 5 s (numerical value 5000)
K
R
= 1 (numerical value 100)
T
N
, T
D
= 0
Upper limit of the control zone = 30 _C
Lower limit of the control zone = 30 _C
HKV = 100 % (for 3-step controllers)
Enter the setpoint temperature
.
! The module switches the heating on.
Wait until the actual value has ”settled”
.
Note: the actual value does not need to have reached the setpoint.
Enter setpoint temperature = 1 _C
.
! The module switches the cooling on.
Note:
and only required with 3-step controllers.
The parameters are then obtained from the curve:
T
U
= delay time (in s)
S
K
= maximum slope of the cooling curve (in _C/s)
S
H
= maximum slope of the heating curve (in _C/s)
Time
   !   "#
Tempe-
rature
!
!!"
! "#  "#
!!
!!"

Table of Contents

Other manuals for Siemens SIMATIC S7

Related product manuals