Operation
IP244B
C79000–B8576–C865–01
3–30
3.4.5 Comparison of the Jumper Assignments of 6ES5244-3AA22/-3AB31
Thermocouple mode (delivery state)
6ES5244-3AB31 6ES5244-3AA22
Thermal e.m.f. measurement with reference junction via channel 15
56
78
13 14
15 16
1–2, 3–4, 5–6: 1–1, 2–2, 3–3:
51,2 mV input sensitivity
7–8: not used
9–10, 11–12, 13–14, 15–16: 5–5, 6–6, 7–7, 8–8:
Thermal e.m.f measurement
3
7
8
3
7
8
34
12
X9
Channel 13: 1:400 voltage divider active
R83 and R84 in
delivery state
Channel 14: 1:400 voltage divider active
R85 and R86 in
delivery state
56
Channel 15: Reference point temperature measurement with Pt 100 in
3-wire circuit
Pt 100 mode
6ES5244-3AB31 6ES5244-3AA22
Pt 100 measurement in 4-wire circuit
56
78
13 14
15 16
1–2, 3–4, 5–6:
512 mV input sensitivity
7–8: not used
9–10, 11–12, 13–14, 15–16:
Pt 100 resistance-type sensor
4-wire circuit
3
7
8
3
7
8
34
12
X9
Channel 13: Same sensitivity as selected at X8 (1:400 divider
inactive)
R83 shorted,
R84 removed
34
12
X10
Channel 14: Same sensitivity as selected at X8 (1:400 divider
inactive)
R85 shorted
R86 removed
56
Channel 15: normal input channel
Same sensitivity as selected at X8
General selections
6ES5244-3AB31 6ES5244-3AA22
56
78
1–2: not used 1–1
3–4: jumper D 2–2
5–6: inserted inserted 3–3
7–8: not inserted not inserted 4–4
50 Hz Netzunterdrückung
3
4
3
4
56
78
1–2: not used 1–1
3–4: jumper D (see Programming Instructions) 2–2
5–6: not inserted not inserted 3–3
7–8: inserted inserted 4–4
60 Hz Netzunterdrückung
3
4
3
4
1–2: BASP not effective 4–4
3–4: for test purposes only, must remain open
34
12
X12
1–2: BASP has an effect on digital outputs
3–4: for test purposes only, must remain open