Operation
3–27
IP244B
C79000–B8576–C865–01
3.4.1 Setting the Module Address
Each temperature controller module 244 requires 32 addresses for transferring the necessary
parameters. Only the start address of each module must be set. The next 31 addresses are
assigned by internal decoding and are no longer available to other modules. The addresses can
be selected in multiples of 32.
P
E
S
P
2
8
2
9
2
10
2
11
256
Break
2
8
...
2
11
2
5
2
6
2
7
32 64 128
87654321
PESP
break
87654321
DIL switch A 76 DIL switch A 77
for ADB 8 ... 11 for ADB 5 ... 7
Switch A 77
No. EU CU
5 off on
7onon
8onon
5 off on
7onon
8onon
5onon
7onon
8 off off
Baugruppenadresse
Einstellen Bereich
über 0..224
A 77
über 128..224
A 77
über 0..224
A 77
Switch A 76
EU CU
2
8
..2
11
2
8
=on
= off 2
9
..2
11
= off
2
8
..2
11
2
8
..2
11
= off = off
2
8
..2
11
2
8
..2
11
= off = off
Module address
Set Range
by 0..224
A 77
by 128..224
A 77
by 0..224
A 77
Address parameter
with FB 162
0
1
2
Proces range
Q area
AG 135 U
AG 155 U
AG 115U
(CPU 945)
only in EU
P area
all PLCs
ABS area
AG 115 U
Example:
The start address of the temperature controller module is n = 160 in the P area of the CU.
Set the switches as follows:
A 77A 76
The next module may then be aasigned from
address 192 (160 + 32) onwards.
1
2
3
4
5
6
7
8
offonoffon