EasyManua.ls Logo

Siemens SIMATIC S7

Siemens SIMATIC S7
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Notes on Controller Settings
4–139
IP244
C79000–B8576–C860–02
4.7 Determining the System Parameters for Purely Cooling
Controllers (when Control Byte 1, Bit 0 = 0 and Bit 2 = 1)
The cooling response of the temperature-controlled system is plotted with a recorder (see also
Fig. 4.8/1).
The procedure is as follows:
enter non-critical control parameters:
T
A
= 0.8 s (numerical value 800)
K
R
= 1 (numerical value 100)
T
N
, T
D
= 0
Upper limit of the control zone = 30 C
Lower limit of the control zone = 30 C
Enter setpoint temperature = 0 C
Allow the temperature to settle to the operating temperature, dependent on external heating
energy supply (e.g. by neighboring heating zones).
Enter setpoint temperature = 1 C
.
The module switches the cooling on.
Caution: during the cooling process the external supply of heating energy must remain
constant (i.e. neighboring heating zones must heat with a constant manipulated
variable).
Temperature
  Time

Fig. 4.8/1 Recorded cooling curve
The parameters can then be determined from the curve:
T
U
= delay time (in s)
S
K
= maximum slope of the cooling curve (in C/s)
T
sta
= start temperature (in C).
The temperature T
COOL
(in C) of the cooling medium must also be determined.

Table of Contents

Other manuals for Siemens SIMATIC S7

Related product manuals