Description of the Firmware
4–17
IP244
C79000–B8576–C860–02
1.2.2 Mode of Operation
Fig. 1.2.1/1 shows the structure of the temperature controller with self-tuning function.
In addition to the PID controller as described in Chapter 1, the following functions are also included:
self-tuning,
parameter monitoring,
PID controller in rugged design.
The ”self-tuning function” performs a process identification and determines the optimum
controller parameters. It also controls the process during the self-tuning phase. On
completion of the self-tuning, the rugged PID controller takes over process control.
The ”parameter monitoring” function checks whether the controlled system has changed its
characteristics, if necessary reduces the controller gain and increases the integral action
time.
A rugged PID controller is obtained from the conventional PID control algorithm, which is not
sensitive to small control system changes as caused, for example, by plastic-granulate
change.