Function
5–9
IP244
C79000–B8576–C861–02
BEF: Specification of the command
The following commands are valid without a message number being specified:
KS = KS Cold restart
Messages 0 to 15 and 30 to 42 are transferred. The module
recalculates all the control parameters.
The module identification and the software version are
re-evaluated.
       
       
KS = PA Assign parameters
Messages 0 to 15 and 30 to 42 are transferred. The module
calculates the control parameters taking into account the
previous values.
This command can be executed for all PLCs in the start-up OBs
(OB 20, OB 21, OB 22) and for the S5-115U, S5-135U and
S5-155U also in the cyclic program.
The module identification and the software version are
re-evaluated.
KS = S1 Switch over setpoint to temperature setpoint
KS = S2 Switch over setpoint to lower setpoint
KS = T1 The controller is not disabled if the second tolerances are
violated.
KS = T2 The controller is disabled if the second tolerances are violated
KS = G1 Do not output the averaged manipulated variable.
If a thermocouple fails, a 0% manipulated variable is output
instead of an averaged manipulated variable.
KS = G2 Output the averaged manipulated variable
With the command ”G2”, you can decide whether a manipulated
variable averaged over a specified monitoring time should be
output if a thermocouple fails.