IP244
C79000–B8576–C866–01
7–16
Com-
mand
Meaning possible mes-
sage frame
numbers
B#(0,1) KS – cold restart (only during startup) –
B#(0,2) PA – setting parameters during startup –
B#(0,4) S1 – changeover to setpoint 1 –
B#(0,5) S2 – changeover to setpoint 2 –
B#(0,6) T1 – no controller shutdown when out of tolerance –
B#(0,7) T2 – controller shutdown when out of tolerance –
B#(0,8) G1 – no output of averaged manipulated variable –
B#(0,9) G2 – output of averaged manipulated variable –
B#(1,1) AS – modify setpoint values 0 ... 15
B#(1,2) AE – modify parameters 0 ... 15
B#(2,1) LE – read controller-related data 0 ... 12
B#(2,2) AB – changeover to automatic mode 0 ... 12
B#(2,3) HB – changeover to manual mode 0 ... 12
B#(3,1) IW – read actual value 17 ... 21
B#(4,1) SE – start/stop automatic setting 0 ... 12
ANST: BOOL:
The execution of the command is triggered when the ANST parameter is
set to ’1’. The FC162 function resets the parameter after the command
has been executed or a parameter setting error has occurred.
PAFE: BOOL:
Illgal parameter setting causes the PAFE parameter to be set to ’1’. The
detected error can be read as an error number in the DBB 31 data byte of
the DA-A data block.
Exception: Only the PAFE parameter is set to ’1’ if an illegal or non-exi-
sting data block has been specified. There is no additional fault informa-
tion in this case.
FC162