The following table shows the decimal error numbers (DB-A, DBB 31)
and their meanings.
Error number Meaning
1 Incorrect firmware
4 Module address no multiple of 32
7 DB-B cannot be found; is too short; is write-protected; or is
not sequence-relevant
8 DB-C cannot be found; is too short; is write-protected; or is
not sequence-relevant
9 Illegal command
10 Invalid message frame number (T_NR)
11 DB no. DB-A’ not permitted
12 DB-A’ cannot be found; is too short; is write-protected; or is
not sequence-relevant
13 DB-C’ cannot be found; is too short; is write-protected; or is
not sequence-relevant
14 The command ’LE’ or ’automatic reading after automatic set-
ting’ has been selected in the FC 162, but has not been enabled
on the IP 244 (i.e. bit 2 of master control byte 1 is currently
’0’).
15 Automatic setting in progress, module access is therefore not
possible at the moment (for the commands PA, S1, S2, AS,
AE, AB, or HB).
16 Time-out during cold restart
17 IP 244 time-out
23 DB no. DB-B not permitted
24 DB no. DB-C not permitted
25 DB no. DB-C’ not permitted
The assignments of the other parameters are explained in the Device Ma-
nual (Register 5, Chapter 3.1 ”Invoking the Funktion Block”).
Assigning local variables to parameters is not permitted.
FC162