EasyManua.ls Logo

Siemens SIMATIC S7 - Page 46

Siemens SIMATIC S7
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Description
IP244B
C79000–B8576–C865–01
3–8
Additional error by voltage divider
(channels 13 and 14) 0.25 %
Temperature influence
(0 to 50 mV range)
1
o
/
oo
/ 10 Kelvin
(2 E / 10 Kelvin)
Additional error by temperature influence in channels with
voltage divider (voltage divider temperature coefficient)
0,5
o
/
oo
/ 10 Kelvin
(1 E / 10 Kelvin)
Error message for out-of-tolerance, overrange and open wire
conditions
Yes
Open wire detection Yes for sensors with R
i
<1 kW
Measurement principle integrating
Resolution of measured value (internal) 11 bits + sign (value + sign);
2048 units;
with Pt 100 0...4096 units
Conversion time per channel typ. 50 ms
40 ms with 0
60 ms with 2048 units
80 ms with 4096 units
Integration time
50 Hz mains frequency 20 ms
60 Hz mains frequency 16
2
/
3
ms
Max. cable length
    50 m, screened
for Pt 100 and linear sensors (> 500 mV) 200 m, screened
(recommended max. cable
length that may be exceeded
if appropriate noise suppres-
sion measures have been
taken)
Operation with ungrounded thermocouples possible if the max. common-
mode voltage is not ex-
ceeded.

Table of Contents

Other manuals for Siemens SIMATIC S7

Related product manuals