Installation
3–13
IP244B
C79000–B8576–C865–01
Do not connect a load power supply to pin 20. The connection provides a shortĆcircuitĆ
proof power supply of the contact at pin 1. In S5Ć115, use the adapter casing and conĆ
nect the lines at pins 21 through 37 0 V (M bar), i.e. reference potential.
Without leaving a gap, the 17 digital outputs are assigned consecutively as two- or three-step
controllers according to the configuration. The number of controllers is limited by the digital out-
puts required (maximum 17).
Typical controller assignment
Required: Cascaded control with closed-loop controllers 1, 2, and 3 as three-step controllers
and closed-loop controllers 4, 5, and 6 as two-step controllers. All other controllers are disabled.
The diagram below shows the controller assignments:
DA 8
Analog input
AE 0
AE 3
AE 5
AE 6
AE 2
AE 4
AE 1
DA 10
DA 12
DA 13
DA 14
DA 15
DA 16
Heating
DA 9
Heating
Heating
Controller 0 is the master controller
Controller
0
Heating
Cooling
Heating
DA 11 Cooling
Heating
Cooling
Controller
2
Controller
1
Controller
3
Controller
4
Controller
5
Controller
6
The other analog inputs are used for measuring. The remaining digital outputs are not used.