TUP / TROUBLESHOOTING
5-18
Hardware
and Installation User Manual
5.2.6 Troubleshooting
the Power Supply
Complete the following steps when troubleshooting the power supply:
1. Determine that the power budget has not been exceeded and that the
module
is properly installed.
2. After making sure the battery is on (so the program will not be lost),
disable
all power to the system for at least 90 seconds.
3.
Restore system power
.
4.
If the problem still exists, turn off power to the system.
WARNING
To avoid the potential risk of damage to equipment
or
injury to personnel, always turn off power to
the
system before removing the power supply from the
base.
5. Remove
the power supply from the base.
This step is not required for the
PPX:505–6663
power supply
.
a. Make
sure
the jumper in the back of the module is set to the correct
line
voltage.
b. If the voltage has been set incorrectly, wait at least one minute
before touching the jumper. Then move the jumper to the
appropriate
quick-connect pin.
6. Make sure the wires attached to the terminal screws on the bezel are
secure
and that the user
-supplied power source is functional.
7. Check
to see that the fuse (located on the bezel) has not opened. Replace
the
fuse, if necessary
, with the appropriate fuse.
a. Using a flat-blade screwdriver, twist the fuse holder once,
counter-clockwise,
to remove the fuse holder
.
b. To replace the fuse holder, insert, push, and turn clockwise to
secure.
8. Replace
the power supply and enable power to the system.
9.
If the power supply continues to malfunction, replace it.
If replacing the fuse does not solve the problem, and the power source is
correctly connected, then the power supply module should be returned for
repair.
Contact your local distributor for assistance.
Artisan Scientific - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisan-scientific.comArtisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC TI525 and is the answer not in the manual?

Siemens SIMATIC TI525 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC TI525
CategoryControl Unit
LanguageEnglish

Related product manuals