Description of system components 
  8.14 Configuration information for SIMOCODE pro V when using an older basic unit 
SIMOCODE pro 
System Manual, 05/2019, A5E40507475002A/RS-AD/004 
155 
8.14  Configuration information for SIMOCODE pro V when using an older 
basic unit 
 
Note 
Restrictions for the SIMOCODE pro V device series 
The restrictions mentioned here apply to the SIMOCODE
 pro V High Performance device 
ies with the following product versions: 
  SIMOCODE pro V PB: Before E15 
  SIMOCODE pro V PN: Before E10 
  SIMOCODE pro V MR: Before E03 
Devices with the stated product versions or later can b
e used without restriction with an 
operator panel with display
 and 2nd generation current/voltage measuring modules. 
You will find usage restrictions concerning the operator panel with display in Chapter 
Description of the operator panel with display (Page 88). 
Use of a decoupling module and/or an operator panel with display 
If you want to use an operator panel with display and/or a decoupling module in the 
SIMOCODE pro V system, then the following configuration instructions concerning the type 
and number of connectable expansion modules must be observed. 
The following table shows the maximum possible configuration with expansion modules for 
the various combinations (✓ = possible, - = not possible):