Technical data 
  15.11 Typical reaction times 
SIMOCODE pro 
System Manual, 05/2019, A5E40507475002A/RS-AD/004 
365 
15.11  Typical reaction times 
15.11.1  Typical reaction times of the SIMOCODE pro C/V device series 
Table 15- 1  Typical reaction times of SIMOCODE pro C device series  
Basic unit: 
Thermistor: 
Set delay time 
400 ms 
30 ms  10 ms 
- 
Current measurement: 
Internal ground fault: 
200 ms 
300 ms ... 600 ms + set delay 
- 
- 
 
Table 15- 2  Typical reaction times of SIMOCODE pro V device series 
1)
 
 
 
 
Basic unit: 
Thermistor: 
Set delay time 
400 ms 
5 ms  10 ms 
- 
2), 4)
Current measurement: 
Voltage measurement: 
Active power / cos phi: 
300 ms 
300 ms 
1000 ms 
3)
200 ms 
200 ms 
200 ms 
3)
- 
- 
- 
Ground-fault module / external 
100 ms 
3)
  - 
Digital modules: 
•  24 V DC version 
•  110 V - 240 V AC/DC version 
 
15 ms + delay time 
50 ms + delay time 
 
25 ms 
25 ms 
DM-F PROFIsafe  15 ms + delay time  30 ms 
1) Based upon a typical hardware set-up: Basic unit + current measuring module + 
2 expansion modules 
Reaction time = inputs conversion time + internal processing time + outputs conversion time