Commissioning, service, troubleshooting   
13.2 Commissioning 
  SIMOCODE pro 
270  System Manual, 05/2019, A5E40507475002A/RS-AD/004 
13.2.4  Commissioning with EtherNet/IP 
13.2.4.1  EtherNet/IP commissioning steps 
Please observe the information in Chapter General information about commissioning and 
service (Page 255). 
To commission SIMOCODE pro, proceed as follows: 
Table 13- 12  Commissioning the basic unit  
1  Switch on the power supply. In a fault-free state, the following LEDS should light up green: 
•  "Device" (lights up) 
•  "PORT 1 / PORT 2" when the Ethernet cable is connected (lighted or flashing). 
Continue with step 2. 
Otherwise, carry out diagnostics according to the LED display. For more information, see Chapter 
Diagnostics via 
LED display on the basic unit and on the operator panel with EtherNet/IP (Page 274). Try to rectify the fault. 
2  If you want to make SIMOCODE pro available to EtherNet/IP, you must set the IP parameters and the device 
name. For more information, see Chapter Setting IP parameters and EIP device name (Page 271). 
3  Parameterize SIMOCODE pro or check the existing parameterization, e.g. with a PC on which SIMOCODE ES 
software is installed. For this, connect the PC / PG to the system interface with the PC cable (see the figure below). 
 
 
Figure 13-5  Connecting a PC to the basic unit