Commissioning, service, troubleshooting 
  13.3 Service 
SIMOCODE pro 
System Manual, 05/2019, A5E40507475002A/RS-AD/004 
285 
 
 
Tightening torque of the screws 
To ensure that the panel will function correctly and is sealed to comply with IP54, the 
tightening torque of the screws provided must not be set too high when mounting and the 
seal must be properly fitted. 
 
 pro 3UF7 system operator panel is not compatible with 
 DP 3UF5, and vice versa.  
13.3.5  Restoring factory settings 
With the factory settings, all parameters are reset to the factory values. 
Restoring the factory settings with the TEST / RESET button on the basic unit  
Proceed as follows (also deletes any previous password setting!): 
Table 13- 24  Restoring the factory settings with the TEST / RESET button 
Switch off the supply voltage for the basic unit. 
Press the TEST / RESET button on the basic unit and keep it pressed. 
Switch on the supply voltage for the basic unit. The "Device" LED lights up yellow. 
Release the TEST / RESET button after approx. two seconds. 
Press the TEST / RESET button again after approx. two seconds. 
Release the TEST / RESET button after approx. two seconds. 
Press the TEST / RESET button again after approx. two seconds. 
The factory setting is restored. 
 
 
Note 
If any of the steps stated above are not carried out correctly, the basic unit will revert to 
normal oper
ation. 
 
 
Note 
This function is always active, irrespective of the "TEST
 / RESET keys disabled" parameter.