Commissioning, service, troubleshooting   
13.2 Commissioning 
  SIMOCODE pro 
274  System Manual, 05/2019, A5E40507475002A/RS-AD/004 
13.2.4.4  Diagnostics via LED display on the basic unit and on the operator panel with 
EtherNet/IP 
The basic unit and the operating panel have LEDs for displaying specific device states:  
Table 13- 14  Diagnostics via LED display 
Corrective measures for faults 
Device  Device 
status 
Green flickering  Internal fault  Send back the basic unit! 
Yellow  Memory module recognized, TEST/RESET 
buttons control the memory module 
_ 
Yellow flashing  Memory module read in; factory settings 
configured (duration: 3 s) 
_ 
Yellow flickering  Memory module programmed 
_ 
Device defective (also GEN. FAULT on) 
Red – flashing  Memory module or expansion modules 
defective (also GEN. FAULT on - flashing) 
Reprogram/replace the memory 
module, replace the expansion 
Off  Supply voltage too low  Check whether the supply 
voltage is connected/switched 
PE energy saving mode active 
Bus  Bus status  Off  No communication with a controller active  Connect the bus or check 
Ethernet parameters (IP 
Green flashing  Communication with a controller active 
(e.g. Rockwell Automation controller)  
_ 
GEN. 
FAULT 
Fault 
status 
Fault pending; reset has been saved 
Rectify fault, e.g., overload 
Fault pending; reset has not been saved 
PORT1 
(only on 
basic unit) 
Bus status 
Ethernet connection available 
Off  No Ethernet connection available  Check the Ethernet connection 
Station flash test for device location active 
PORT2 
(only on 
basic unit) 
Bus status 
Ethernet connection available 
Off  No Ethernet connection available  Check the Ethernet connection 
Station flash test for device location active