Description of system components 
 8.5 Current / voltage measuring modules (UM, UM+) for the SIMOCODE pro V High Performance device series 
SIMOCODE pro 
System Manual, 05/2019, A5E40507475002A/RS-AD/004 
135 
8.5  Current / voltage measuring modules (UM, UM+) for the 
SIMOCODE pro V High Performance device series 
Variants  
Two device generations of the current / voltage measuring modules are available: 
1st generation: UM, MLFB ending in 000 (e.g. 3UF71101AA000). 
A decoupling module may be required when using these current / voltage measuring 
modules. See Chapter Decoupling module (DCM) for 1st generation current/voltage 
measuring modules (e.g. 3UF711.1AA000) (Page 142). 
2nd generation: UM+, MLFB ending in 010 (e.g. 3UF71101AA010). 
These current / voltage measuring modules do not require a decoupling module. 
Function 
The SIMOCODE pro V High Performance device series allows use of a current / voltage 
measuring module instead of a current measuring module. In addition to measuring the 
motor current, current / voltage measuring modules also enable:  
●  Monitoring voltages up to 690 V (UM, UM+)  
●  Calculation and monitoring of power and cos phi (UM, UM+)  
●  Determining the frequency (UM+) 
●  Monitoring the phase sequence (UM, UM+)  
With SIMOCODE ES (TIA Portal), you can define under "Parameters → Device 
configuration → Display voltage" whether the phase voltage or line-to-line voltage is to be 
used system-wide (when using a SIMOCODE pro V High Performance basic unit from 
firmware version V3.0). 
Current / voltage measuring modules are available for the following current ranges: 
 
Through-hole technology 
or bus connection system 
UM 
2.4 to 25 A  ✓  —  — 
UM+