Commissioning
8-123
E Siemens AG, 2003 All rights reserved
SIMOTION C230-2, 04.2003 Edition
8.7 Resetting the C230-2 to the default setting as delivered
Overview
You can reset the C230-2 to the as delivered state (default setting) via operations
on the mode selector.
The following data is deleted:
S Configuration data
S Programs
S Parameterizations
S Technology packages
S Retain variables
Retain variables are variables that are defined as Non-volatile variables in the
user program using the key word Retain.
S Diagnostics buffer
S Clock
The following data is retained:
S SIMOTION Kernel
The following data is reset:
S Baud rate = 1.5 Mbit/s
S PROFIBUS address for the interfaces X8 = 2 and X9 = 2
S IP address = 169.254.11.22, subnet dialog box = 255.255.0.0 and
router address = 169.254.11.22
Operations on the mode selector
Proceed as follows:
1. Switch off the power supply for the C230-2.
2. Remove the Micro Memory Card from the C230-2.
3. Turn the key on the mode selector to the MRES position. Hold the key in this
position and switch on the power supply for the C230-2. When the STOPU
LED flickers, turn the key to the STOP position again.

Table of Contents

Other manuals for Siemens SIMOTION C230-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOTION C230-2 and is the answer not in the manual?

Siemens SIMOTION C230-2 Specifications

General IconGeneral
BrandSiemens
ModelSIMOTION C230-2
CategoryController
LanguageEnglish

Related product manuals