Addressing the I/O
5-73
E Siemens AG, 2003 All rights reserved
SIMOTION C230-2, 04.2003 Edition
Module initial addresses
Table 5-1 shows the assignment of module initial addresses to slot numbers and
racks.
In the case of input/output modules, the input addresses and output addresses
start from the same module initial address.
Table 5-1 Module initial addresses of signal modules
Rack
Module Slot number
initial ad-
dresses
1 2 3 4 5 6 7 8 9 10 11
0
Digital
Analog
1)
PS C230-2
IM 365
S
0
256
4
272
8
288
12
304
16
320
20
336
24
352
28
368
1 Digital
Analog
1)
IM 365
R
32
384
36
400
40
416
44
432
48
448
52
464
56
480
60
496
1)
The FM and CP modules are assigned to the analog address range.