Interfaces
3.3 Ethernet interfaces
SIMOTION D4x5-2
42 Manual, 11/2010
DRIVE-CLiQ pin assignment
Table 3- 4 DRIVE-CLiQ interface X100 – X105
PIN Signal name Signal type Meaning
1 TXP O Transmit data +
2 TXN O Transmit data -
3 RXP I Receive data +
4 ---- ---- Reserved, do not use
5 ---- ---- Reserved, do not use
6 RXN I Receive data -
7 ---- ---- Reserved, do not use
8 ---- ---- Reserved, do not use
A + (24 V) VO Power supply for DRIVE-CLiQ, 450 mA maximum
B M (0 V) VO Ground to 24 V
Signal type: I = Input; O = Output; VO = Voltage Output
Additional references
●
SINAMICS S120 Control Units and Additional System Components
Manual
●
SINAMICS S120 Booksize Power Units
Manual
●
SINAMICS S120 for AC Drives
Manual
●
SINAMICS S120
Commissioning Manual
●
Terminal Modules TM15 and TM17 High Feature
Commissioning Manual
●
TM15/TM17 High Feature
Manual
● For order numbers, refer to the list of references (separate document).
3.3 Ethernet interfaces
Interfaces for connection to Industrial Ethernet
Industrial Ethernet is a communication network with a transmission rate of
10/100/1000 Mbit/s.
SIMOTION D4x5-2 offers the following functions via Ethernet interfaces:
● Communication with STEP 7 and SIMOTION SCOUT
● Communication between SIMOTION and SIMATIC NET OPC
The following software must be installed on the PG/PC for this function:
"SIMATIC NET SOFTNET-S7 (S7-OPC server)"
● Connection of HMI systems