Supplementary system components
6.4 CX32-2 controller extension
SIMOTION D4x5-2
96 Manual, 11/2010
6.4.2.3 DRIVE-CLiQ interface
Table 6- 13 DRIVE-CLiQ interface X100 – X103
Pin Signal name Technical specifications
1 TXP Transmit data +
2 TXN Transmit data -
3 RXP Receive data +
4 Reserved, do not use
5 Reserved, do not use
6 RXN Receive data -
7 Reserved, do not use
8 Reserved, do not use
A + (24 V) Power supply
B M (0 V) Electronic ground
Dust protection blanking plugs for sealing unused DRIVE-CLiQ ports:
Three blanking plugs contained in the CX32-2 scope of delivery
Blanking plugs (50 pcs) order number: 6SL3066-4CA00-0AA0
6.4.2.4 Digital inputs/outputs (X122)
Interface characteristics
Sensors and actuators can be connected to the X122 connector via digital inputs and
outputs.
Table 6- 14 X122 wiring
Characteristics Type
Connector type Mini Combicon
Connectable cable types:
- Rigid
- Flexible
- Flexible, with end sleeve without plastic sleeve
- AWG/kcmil
Conductor cross-sections:
0.2 mm
2
to 1 mm
2
0.2 mm
2
to 1.5 mm
2
0.25 mm
2
to 1.5 mm
2
24 to 16
Stripped length 8 mm
Tool Screwdriver 0.4 x 2.0 mm
Max. current carrying capacity (ground) 6 A
Position of the connector
The X122 connection is on the front side of the CX32-2 at the top, see appropriate figure in
Chapter Overview of interfaces (Page 94).