When selecting an application class, the inverter assigns the motor control with the appropriate
default settings:
● Standard Drive Control (Page 162)
● Dynamic Drive Control (Page 164)
● Start quick commissioning and select the application class (Page 154)
Depending on the particular Power Module, the inverter skips selecting the application
class. If the BOP-2 does not display step DRV APPL, then continue commissioning as
described under "Expert".
Select the suitable application class
When selecting an application class, the inverter assigns the appropriate settings to the motor
control.
Application class Standard Drive Control Dynamic Drive Control
Properties
● Typical settling time after a speed change:
100 ms … 200 ms
● Typical settling time after a load surge: 500 ms
6SHHG
/RDG
0RWRU
WRUTXH
W
W
W
PV
● Standard Drive Control is suitable for the
following requirements:
– Motor power ratings < 45 kW
– Ramp-up time 0 → rated speed
(depending on the motor power rating):
1 s (0.1 kW) … 10 s (45 kW)
– Applications with increasing load torque
without load surges
● Standard Drive Control is insensitive with
respect to imprecise setting of the motor data
● Typical settling time after a speed change:
< 100 ms
● Typical settling time after a load surge: 200 ms
6SHHG
/RDG
0RWRU
WRUTXH
W
W
PV
● Dynamic Drive Control controls and limits the
motor torque
● Torque accuracy that can be achieved: ± 5% for
15 % … 100 % of the rated speed
● We recommend Dynamic Drive Control for the
following applications:
– Motor power ratings > 11 kW
– For load surges 10 % … >100 % of the rated
motor torque
● Dynamic Drive Control is necessary for a ramp-
up time 0 → rated speed (dependent on the rated
motor power): < 1 s (0.1 kW) … < 10 s (132 kW).
Application exam‐
ples
● Pumps, fans, and compressors with flow
characteristic
● Pumps and compressors with displacement
machines
Power Modules
that can be operat‐
ed
PM240‑2, PM240P-2 PM240‑2, PM240P-2 PM330
Max. output fre‐
quency
550 Hz 240 Hz 150 Hz
Commissioning
5.4 Quick commissioning using the BOP-2 operator panel
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE 161