6.17.2 Invert setpoint
The inverter provides an option to invert the setpoint sign using a bit. As an example, the
setpoint inversion is shown through a digital input.

S

[
\
[
\
W
\\[[

To invert the setpoint via an external signal, interconnect parameter p1113 with a binary signal,
e.g. digital input 1.
Table 6-38 Application example for inverting the setpoint
Parameter Remark
p1113 Setpoint inversion (factory setting depends on the inverter)
p1113 = 722.1 Digital input 1 = 0: Setpoint remains unchanged.
Digital input 1 = 1: Inverter inverts the setpoint.
p1113 = 2090.11 Invert setpoint via control word 1, bit 11.
Advanced commissioning
6.17 Setpoint calculation
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE 267