7.5 Write protection
The write protection prevents unauthorized changing of the inverter settings. If you are working
with a PC tool, such as STARTER, then write protection is only effective online. The offline
project is not write-protected.
Write protection is applicable for all user interfaces:
Operator Panel BOP-2 and IOP‑2
STARTER or Startdrive PC tool
Parameter changes via fieldbus
No password is required for write protection.
Activate and deactivate write protection
Procedure with STARTER
Proceed as follows to activate or deactivate the write protection:
1. Go online.
2. Open the shortcut menu of the
required inverter.
3. Activate or deactivate write protection.
4. Press the “Copy RAM to ROM” button
to retentively save the settings .
You have activated or deactivated write protection.
Active write protection can be identified as in the expert list the input fields of adjustable
parameters p … are shaded gray.
Parameters
r7760 Write protection/know-how protection status
.00 1 signal: Write protection active
p7761 Write protection (factory setting: 0)
0: Deactivate write protection
1: Activate write protection


Saving the settings and series commissioning
7.5 Write protection
Converter with the CU230P-2 Control Units
386 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE