4.4.2 TT line system
In a TT line system, the transformer grounding
and the installation grounding are independ‐
ent of one another.
There are TT line supplies where the neutral
conductor N is either transferred – or not.
7UDQVIRUPHURU
JHQHUDWRU
7RWKHV\VWHP
([DPSOH7UDQVIHURI1JURXQGHGQHXWUDO
SRLQW
/
/
/
1
3(
Inverter operated on a TT line system
Inverter with integrated or external line filter:
Operation on TT line systems with grounded neutral point permissible.
Operation on TT line systems without grounded neutral point not permissible.
Inverter without line filter:
Operation on all TT line systems permissible.
For installations in compliance with IEC, operation on a TT line system is permissible. For
installations in compliance with UL, operation on a TT line system is not permissible.
Installing
4.4 Connecting the line supply and motor
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE 85