10.6.4 Current derating depending on the pulse frequency, 200 V inverters
Article number LO
power
[kW]
LO base load output current [A]
Pulse frequency [kHz] 2 4
*)
6 8 10 12 14 16
6SL3210-1PB13-0 . L0 0.55 3.2 3.2 2.7 2.2 1.9 1.6 1.4 1.3
6SL321 . -1PB13-8 . L0 0.75 4.2 4.2 3.6 2.9 2.5 2.1 1.9 1.7
6SL3211-1PB15-5 . L0 1.1 6 6 5.1 4.2 3.6 3 2.7 2.4
6SL3210-1PB17-4 . L0 1.5 7.4 7.4 6.3 5.2 4.4 3.7 3.3 3
6SL321 . -1PB21-0 . L0 2.2 10.4 10.4 8.8 7.3 6.2 5.2 4.7 4.2
6SL3210-1PB21-4 . L0 3 13.6 13.6 11.6 9.5 8.2 6.8 6.1 5.4
6SL321 . -1PB21-8 . L0 4 17.5 17.5 14.9 12.3 10.5 8.8 7.9 7
6SL3210-1PC22-2 . L0 5.5 22 22 18.7 15.4 13.2 11 9.9 8.8
6SL3210-1PC22-8 . L0 7.5 28 28 23.8 19.6 16.8 14 12.6 11.2
6SL3210-1PC24-2 . L0 11 42 42 35.7 29.4 25.2 21 18.9 16.8
6SL3210-1PC25-4 . L0 15 54 54 45.9 37.8 32.4 27 24.3 21.6
6SL321 . -1PC26-8 . L0 18.5 68 68 57.8 47.6 40.8 34 30.6 27.2
6SL3210-1PC28-0 . L0 22 80 80 68 56 48 40 36 32
6SL321 . -1PC31-1 . L0 30 104 104 88.4 72.8 62.4 52 46.8 41.6
6SL3210-1PC31-3 . L0 37 130 130 110.5 91 --- --- --- ---
6SL3210-1PC31-6 . L0 45 154 154 130.9 107.8 --- --- --- ---
6SL321 . -1PC31-8 . L0 55 178 178 151.3 124.6 --- --- --- ---
*) Factory setting
The permissible motor cable length depends on the particular cable type and the pulse frequency that
has been selected
Technical data
10.6 Technical data, PM240-2 Power Module
Converter with the CU230P-2 Control Units
486 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE