EasyManua.ls Logo

Siemens SINAMICS G120 - General Technical Data, PM230

Siemens SINAMICS G120
550 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10.3.4 General technical data, PM230
Property Version
Line voltage 380 … 480 V 3 AC ± 10%
Output voltage 3-phase 0 VAC … input voltage x 0.95 (max.)
Input frequency 50 Hz … 60 Hz, ± 3 Hz
Output frequency 0 Hz … 550 Hz, depending on the control mode
Power factor λ 0.9
Line impedance Uk ≤ 1%, line reactor not permissible
Inrush current < LO base load input current
Pulse frequency (factory set‐
ting)
4 kHz
The pulse frequency can be increased in 2 kHz steps up to 16 kHz (up to 8 kHz for 55 kW
and 75 kW). An increase in the pulse frequency results in a lower output current.
Electromagnetic compatibility Devices with filters in compliance with EN 61800-3: 2004 are suitable for Category C2 en‐
vironments.
Braking methods DC braking
Degree of protection IP20 built-in units
PT devices
IP20 when mounted in a control cabinet
IP54 on the control cabinet wall
Operating temperature at LO base load power without derating 0° C … +40° C
HO base load power without derating 0° C … +50° C
LO/HO base load power with derating: Up to 60° C
Restrictions for special ambient conditions (Page 510)
Storage temperature -40° C … +70° C
Relative humidity < 95% - condensation not permissible
Pollution Protected according to pollution degree 2 according to EN 61800-5-1: 2007
Ambient conditions Protected against damaging chemical substances according to environmental class 3C2
according to EN 60721-3-3: 1995
Shock and vibration
Long-term storage in the transport packaging according to Class 1M2 according to
EN 60721‑3‑1: 1997
Transport in the transport packaging according to Class 2M3 according to EN 60721-3-2:
1997
Vibration during operation according to Class 3M2 according to EN 60721-3-3: 1995
Installation altitude without derating:
with derating:
up to 1000 m above
sea level
up to 4000 m above
sea level
Restrictions for special ambient condi‐
tions (Page 510)
Permissible short-circuit cur‐
rent
Frame size D ... F: 65 kA
1)
Overvoltage category Supply circuits:
Non-supply circuits:
Overvoltage category III
Overvoltage category II
Standards UL
1),2)
, CE, C-tick
The drive only satisfies the UL requirements when UL-certified fuses are used.
1)
If fuse-protected with a listed Class J or 3NE1 fuse, rated voltage 600 VAC with the rated current of the specific inverter.
2)
UL available soon for frame sizes D … F
Technical data
10.3 Technical data, PM230 Power Module
Converter with the CU230P-2 Control Units
446 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE

Table of Contents

Other manuals for Siemens SINAMICS G120

Related product manuals