6.4.3 Two-wire control, method 3
&ORFNZLVH
&RXQWHUFORFNZLVH
212))
&RXQWHUFORFNZLVH
212))
&ORFNZLVH
6SHHGVHWSRLQW
W
W
W
672367236723
Figure 6-8 Two-wire control, method 3
Commands "ON/OFF1 clockwise rotation" and "ON/OFF1 counter-clockwise rotation" switch
on the motor - and simultaneously select a direction of rotation. The inverter accepts a new
command at any time, independent of the motor speed.
Table 6-15 Function table
ON/OFF1 clockwise rota‐
tion
ON/OFF1 counter-clock‐
wise rotation
Function
0 0 OFF1: The motor stops.
1 0 ON: Clockwise motor rotation.
0 1 ON: Counter-clockwise motor rotation.
1 1 OFF1: The motor stops.
Table 6-16 Select two-wire control, method 3
Parameter Description
p0015 = 18 Macro drive unit
You must carry out quick commissioning in order to set parameter p0015.
Assigning digital inputs DI to the commands:
DI 0: ON/OFF1 clockwise rotation
DI 1: ON/OFF1 counter-clockwise rotation
Table 6-17 Changing the assignment of the digital inputs
Parameter Description
p3330[0 … n] = 722.x BI: 2/3 wire control command 1 (ON/OFF1 clockwise rotation)
p3331[0 … n] = 722.x BI: 2/3 wire control command 2 (ON/OFF1 counter-clockwise rotation)
Example: p3331 = 722.0 ⇒ DI 0: ON/OFF1 counter-clockwise rotation
Advanced commissioning
6.4 Controlling clockwise and counter-clockwise rotation via digital inputs
Converter with the CU230P-2 Control Units
214 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE