Installing
4
4.1 EMC-compliant setup of the machine or plant
The inverter is designed for operation in industrial environments where strong electromagnetic
fields are to be expected.
Reliable and disturbance-free operation is only guaranteed for EMC-compliant installation.
To achieve this, subdivide the control cabinet and the machine or system into EMC zones:
EMC zones
)XVHVVZLWFKHVDQG
FRQWDFWRUV
9SRZHUVXSSO\
+LJKHUOHYHOFRQWURO
V\VWHP
&RQQHFWLRQRIVHQVRUV
HJSRVLWLRQSUHVVXUHRU
WHPSHUDWXUH
/LQHUHDFWRURUOLQHILOWHU
,QYHUWHU
%UDNLQJUHVLVWRU
2XWSXWUHDFWRURU
VLQHZDYHILOWHU
&RQWUROFDELQHW
/LQHVXSSO\
'ULYHQPDFKLQH
Figure 4-1 Example of the EMC zones of a plant or machine
Inside the control cabinet
Zone A: Line supply connection
Zone B: Power electronics
Devices in Zone B generate energy-rich electromagnetic fields.
Zone C: Control and sensors
Devices in Zone C do not generate any energy-rich electromagnetic fields themselves, but
their functions can be impaired by electromagnetic fields.
Outside the control cabinet
Zone D: Motors, braking resistors
Devices in Zone D generate electromagnetic fields with a significant amount of energy
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE 57