10.4.5 General technical data, 690 V inverters
Property Version
Line voltage 3 AC 500 V … 690 V ± 10% (in operation -20% < 1 min)
with Class J fuses, maximum 600 V
Line system configurations Grounded TN/TT line systems or non-grounded IT line systems
Line impedance Uk < 4%, line reactor is not required
Power factor λ > 0.9
Output voltage 3 AC 0 V … 0.95 × input voltage (max.)
Input frequency 50 Hz … 60 Hz, ± 3 Hz
Output frequency 0 … 550 Hz, depending on the control mode
Inrush current < LO base load input current
Overvoltage category ac‐
cording to EN 61800-5-1
III for line supplies
Pulse frequency 2 kHz (factory setting), can be adjusted to 4 kHz
If you increase the pulse frequency, the inverter reduces the maximum output current.
Short-circuit current rating
(SCCR) and branch protec‐
tion
≤ 100 kA rms
Branch protection and short-circuit strength according to UL and IEC (https://
support.industry.siemens.com/cs/ww/en/view/109479152)
Braking methods DC braking, compound braking
Degree of protection ac‐
cording to EN 60529
IP20; must be installed in a control cabinet
Protection class according
to EN 61800-5-1
The inverters are devices with protection class I
Touch protection according
to EN 50274
DGUV regulation 3 when used for the intended purpose
Cooling in compliance with
EN 60146
Forced air cooling AF
Technical data
10.4 Technical Data, PM240P-2 Power Module
Converter with the CU230P-2 Control Units