6.18 PID technology controller
The technology controller controls process variables, e.g. pressure, temperature, level or flow.
3XPS
6SHHGFRQWUROOHU
$FWXDOYDOXH
/HYHOVHWSRLQW
3,'WHFKQRORJ\
FRQWUROOHU
6SHHGVHWSRLQW
Figure 6-30 Example: Technology controller as a level controller
Simplified representation of the technology controller
The technology controller is implemented as a PID controller (controller with proportional,
integral, and derivative action).
/LPLWDWLRQ
6FDOLQJ
,QYHUVLRQ
)XQFWLRQI[
2XWSXW
VLJQDO
6WDUWLQJYDOXH
U
5HVSRQVHWR
HUURUV
$FWXDOYDOXH
2XWSXWVLJQDO
ZLWKHUURU
2SHUDWLRQLVHQDEOHG
WKHPRWRULVVZLWFKHG
RQ
6PRRWKLQJ
3UHSDUDWLRQ
(QDEOH
&RQWUROOHU
HQDEOH
5DPSXSUDPS
GRZQWLPH
5DPSGRZQWLPH
5DPSXSWLPH
6HWSRLQW
6HWSRLQW
6FDOLQJ
S
S
S
S
S
S
S
S
S
.
3
7
G
7
,
The inverter uses the start value when all the following conditions are simultaneously satisfied:
The technology controller supplies the main setpoint (p2251 = 0).
The ramp-function generator output of the technology controller has not yet reached the start value.
Figure 6-31 Simplified representation of the technology controller
The settings required as a minimum are marked in gray in the function diagram: Interconnect
setpoint and actual values with signals of your choice, set the ramp-function generator and
controller parameters K
P
, T
I
and T
d
.
3,'
Advanced commissioning
6.18 PID technology controller
Converter with the CU230P-2 Control Units
274 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE