Advanced settings
You can debounce the digital input signal using parameter p0724.
For more information, please see the parameter list and the function block diagrams 2220 f of
the List Manual.
Overview of the manuals (Page 537)
Analog inputs as digital inputs
$,
',
',
$,
9RXW
9RXW
*1'
U
U
 $,
$,

%,S[[[[
8,
$,
$,
To use an analog input as additional digital input,
you must interconnect the corresponding status pa‐
rameter r0722.11 or r0722.12 with a binector input
of your choice.
You may operate the analog input as digital input
with 10 V or with 24 V.
NOTICE
Overcurrent at an analog input
If the analog input switch is set to "Current input" (I), a 10V or 24V voltage source results in
an overcurrent at the analog input. An overcurrent condition destroys the analog input.
If you use an analog input as a digital input, then you must set the analog input switch to
"Voltage" (U).
Advanced commissioning
6.3 Adapt the default setting of the terminal strip
Converter with the CU230P-2 Control Units
200 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE