Application example: Defining the function of an analog output

$2
U
S>@
To output the inverter output current via analog output 0, you
must interconnect AO 0 with the signal for the output current.
Set p0771 = 27.
Advanced settings
You can manipulate the signal that you output via an analog output, as follows:
Absolute-value generation of the signal (p0775)
Signal inversion (p0782)
Additional information is provided in the parameter list of the List Manual.
Advanced commissioning
6.3 Adapt the default setting of the terminal strip
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE 209