Property Version
Ambient conditions in operation
Installation altitude Up to 1000 m above sea level without derating,
> 1000 m Restrictions for special ambient conditions (Page 510)
Climatic ambient conditions
1)
Temperature range without derating
2)
LO base load power: 0 °C...40 °C
HO base load power: 0 °C...40 °C
For higher temperatures.
Restrictions for special ambient conditions (Page 510)
Relative humidity: 5 … 95%, condensation not permitted
Oil mist, salt mist, ice formation, condensation, dripping water, spraying water, splashing
water and water jets are not permitted
Mechanical ambient condi‐
tions
FSA … FSF: Vibration levels permissible according to Class 3M1 to EN 60721-3-3
FSA … FSC: Shock, permissible according to Class 3M2 to EN 60721-3-3
FSD … FSF: Shock permissible according to Class 3M1 to EN 60721-3-3
Protection against chemical
substances
Protected according to 3C2 to EN 60721‑3‑3
Biological environmental
conditions
Suitable according to 3B1 to EN 60721‑3‑3
Pollution Suitable for environments with degree of pollution 2 according to EN 61800-5-1
Cooling Forced air cooling AF, according to EN 60146
Cooling air clean and dry air
1)
Increased ruggedness regarding temperature range and relative humidity; therefore better than Class 3K3 to EN 60721-3-3
2)
Observe the permissible ambient temperatures for the Control Unit and possibly the operator panel (IOP-2 or BOP‑2).
Technical data
10.3 Technical data, PM230 Power Module
Converter with the CU230P-2 Control Units
440 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE